2016年9月23日星期五

HVJ3 – 7.2 KV Vacuum Contactor

HVJ3 – 7.2 KV Vacuum Contactor


The vacuum contactor is mainly used in the power system with AC 50Hz and rated voltage 7.2kV, for making or breaking circuit and to make electromagnetic starter with suitable protective device and F-C switchgear.


E-mail:  info@Jucro.com

ModelRated voltage(v)
Rated current
Main circuit(A)
Parameter of main contacts
Power frequency
Withstand voltage
V(effective value)
Main
circuit
Control
circuit
Clearance
(mm)
Overtravel
(mm)
pressure
(N)
Main
circuit
Auxiliary
circuit
Control
circuit
HVJ3-7.2/1607200220/1101603.5±0.32±0.2>85N3200025002000
HVJ3-7.2/2507200220/1102503.5±0.32±0.2>85N3200025002000
HVJ3-7.2/4007200220/1104003.5±0.32±0.2>85N3200025002000
HVJ3-7.2/6307200220/1106303.5±0.32±0.2>85N3200025002000

ModelMaking capacityBreaking capacityLimit opening current(A)OverloadMechanism lifeWeight(kg)
HVJ3-7.2/16010Ie,100times8Ie,25times10Ie8Ie,10s1million times25.5
HVJ3-7.2/25010Ie,100times8Ie,25times10Ie8Ie,10s1million times25.5
HVJ3-7.2/40010Ie,100times8Ie,25times10Ie8Ie,10s1million times25.5
HVJ3-7.2/63010Ie,100times8Ie,25times10Ie8Ie,10s1million times25.5
Note: “Ie” represents the rated current of main circuit

2016年8月26日星期五

JN15-12KV Vacuum Circuit Breaker

JN15-12 series indoor high voltage earthing switch is a compositional type, and the technical parameters is corresponding to the requirements of IEC62271-102:2002. It is applicable for three-phase power system of 3-12kv, AC 50HZ. It can be used together with many types high voltage switchgear as a earthing protection unit.
URL: Click Here